SolarSoftwares
Book a demo

What Is Voltage Drop Calculation?

How we keep reviews fair

Quick answer

Voltage drop calculation (also called cable voltage loss) finds how many volts a cable loses as current flows through its resistance. Installers use it to size DC string cables and AC runs. On a DC string, drop = 2 × current × resistance per length × one-way length.

Ready to see how it works?

Tell the SolarSoftwares team which tool you are considering. We reply by email to book your demo.

Book a demo
Jump to a section

Key takeaways

  • For DC and single-phase AC, drop = 2 × current × resistance per length × one-way length. Three-phase uses 1.732 in place of 2.
  • At 10 A, 400 V and 100 ft, copper drops 1.57% on 14 AWG, 0.99% on 12 AWG and 0.62% on 10 AWG.
  • Aluminium has about 1.6 to 1.65 times copper’s resistance (resistivity: 1.58, OpenExamPrep’s Table 8 column: 1.65). So the same size drops about 60% more.
  • Drop falls with current. At half the current, the drop percentage halves (0.31% against 0.62% here).

To work out your own run, use the calculator below. To see which design tools print the drop on each wire run, see the best solar design software.

Voltage drop calculation at a glance

Voltage drop is current times the resistance of the whole circuit. You show it in volts and as a percentage of the circuit voltage.

ItemDetail
FormulaDC and single-phase AC: drop = 2 × I × R × L. Three-phase: 1.732 × I × R × L. L is one-way length. R is resistance per unit length at conductor temperature
Targets in the sources cited3% branch circuit, 5% combined (NEC informational notes, as described by Mayfield Renewables and OpenExamPrep). 2% DC and 1% AC (Penn State). Under 1% desirable, 2% maximum on DC (Huawei)
Where it mattersCable size, energy loss, string mismatch, plan-set conductor tables
Standard or ruleResistances come from NEC Chapter 9 Table 8 as printed in a published sample (see Sources)
In softwareDesign and plan-set tools show it per wire run. Some pick the cable size from a limit

Why does voltage drop matter for installers?

Voltage drop wastes energy as heat. A long run on thin wire can pass 3% (Figure 1).

Huawei’s PV Tech article says a high DC drop also widens the voltage spread between strings on one MPPT. That raises mismatch loss.

Bigger wire lowers the drop but costs more. This page does not cover ampacity. For that, see wire and conductor sizing.

Line chart of DC voltage drop against one-way cable length for five copper sizes from 14 to 6 AWG, with 1%, 2% and 3% reference lines.

Figure 1. At 10 A on 400 V, 14 AWG copper reaches 2% drop at about 127 ft one way. For 12 AWG it is 202 ft and for 10 AWG it is 323 ft. Reference lines mark 1%, 2% and 3%.

How do you calculate voltage drop on a DC string or AC run?

Multiply current by the resistance of the full out-and-back conductor length. Then divide by the circuit voltage. The five steps below work for DC and for small AC runs.

  1. Take the current. Penn State’s notes use the module operating current (Imp) for DC source circuits. For AC, use the inverter’s rated output current.
  2. Take the one-way length from array to inverter. DC and two-wire AC use both conductors, so the loop is twice that length. Penn State says this for DC.
  3. Look up resistance per length. NEC Chapter 9 Table 8 lists uncoated copper 10 AWG at 1.21 ohm per 1,000 ft for solid conductor and 1.24 ohm per 1,000 ft for stranded, the small difference coming from the stranding, not from a coated-versus-uncoated split. The Mike Holt sample page prints the stranded row (1.24). OpenExamPrep’s table shows the solid row (1.21). Match the row to the conductor you are actually pulling, then correct for conductor temperature.
  4. Multiply: drop (V) = 2 × I × R × L ÷ 1,000. R is ohm per 1,000 ft. L is feet.
  5. Divide by the reference voltage and compare with your target. For DC, Penn State uses the string’s maximum-power voltage (Vmp). For AC, use the nominal voltage.

For balanced three-phase, use 1.732 in place of the factor 2 (OpenExamPrep). This is a resistance-only method. It ignores reactance and power factor on AC.

How do copper, aluminium and temperature change the result?

Aluminium drops about 1.6 to 1.65 times as much as copper at the same size. A hotter conductor drops more.

  • Material: HyperPhysics lists resistivity of 1.68e-8 ohm metre for copper and 2.65e-8 for aluminium at 20°C, a ratio of 1.58. OpenExamPrep’s Table 8 aluminium column gives about 1.65 (10 AWG 2.00 against 1.21, 8 AWG 1.26 against 0.764). So one size up is not quite enough: 8 AWG aluminium (1.26 ohm per 1,000 ft) is slightly worse than 10 AWG copper (1.21) in that same table. Aluminium needs a little more than one size up, and ampacity is a separate check.
  • Aluminium on the 250 ft DC run: at 6 AWG it would drop about 1.01% against 0.61% for copper, using our calculator’s 1.64 estimate.
  • Temperature: Table 8 resistances are at 75°C. Note 2 corrects them with R × [1 + 0.00323 × (T − 75)] for copper. For aluminium it uses 0.00333. A 3°C rise adds about 1% to resistance. For 10 AWG copper the factor is 1.048 at 90°C and 0.855 at 30°C.
  • Datasheet cables: Prysmian’s Slim Solar Twin PV sheet lists maximum resistance at 20°C for tinned copper. It is 5.09 ohm per km (4 mm²) and 3.39 (6 mm²). At 70°C the factor is 1.196, using a copper coefficient of 0.00393 per °C (HyperPhysics).

Using 75°C for a cooler cable gives a cautious answer. A cable in hot conduit may run hotter. Check your own conductor temperature.

What voltage drop target should you use?

The sources disagree. Treat each figure as a recommendation, and confirm with your AHJ, the inverter maker and the client contract. None of the figures in the sources is a PV-specific limit.

SourceFigureApplies to
NEC informational notes, as described by Mayfield Renewables and OpenExamPrep3% branch circuit, 5% combined with feeder (attributed to the NEC)General circuits. Recommendation only
Penn State AE 868 course notes3% total (attributed to the NEC). 2% DC plus 1% ACCourse recommendation
Huawei, PV Tech, October 2022Under 1% desirable. 2% not exceededDC cables in PV plants
Aurora PV system losses e-book2% wiring loss for most systems. 1% with thicker wire or short runsLoss assumption in modelling
Easy PV FAQPicks the smallest cable giving under 1% dropEasy PV’s cable-selection rule

Mayfield Renewables (pv magazine USA, 2020) calls 2% a long-held rule of thumb with anecdotal origins. It finds no firm 2% requirement in the NEC. It adds that later code references treat the notes as if they were requirements. So check the edition your AHJ enforces. Its modelling shows the rule no longer fits most commercial and utility projects.

Worked examples: DC string, AC run and metric cable

A 10 A DC string on 400 V loses 0.62% in 100 ft of 10 AWG copper. Over 250 ft it needs 8 AWG to stay near 1%. Each row is computed from the formula.

DC string. Current 10 A, string voltage 400 V, copper at 75°C, Table 8 resistances. The loop is twice the one-way length.

One-way lengthSizeLoop resistance (ohm)Drop (V, %)Within 1% / 2%?
100 ft14 AWG0.6286.28 (1.57%)No / Yes
100 ft12 AWG0.3963.96 (0.99%)Yes / Yes
100 ft10 AWG0.2482.48 (0.62%)Yes / Yes
250 ft10 AWG0.6206.20 (1.55%)No / Yes
250 ft8 AWG0.3893.89 (0.97%)Yes / Yes
250 ft6 AWG0.2452.46 (0.61%)Yes / Yes

AC run. Single-phase 240 V, 30 A, 120 ft one way, copper at 75°C, resistance only.

SizeDrop (V)Drop (%)Within 1%?Within 3%?
10 AWG8.933.72%NoNo
8 AWG5.602.33%NoYes
6 AWG3.541.47%NoYes

Metric cable. DC string, 10 A, 400 V, 50 m one way (100 m loop), tinned copper. Resistance is the maker’s maximum, corrected from 20°C to 70°C.

SizeLoop resistance at 20°C (ohm)Drop at 20°CLoop resistance at 70°C (ohm)Drop at 70°C
4 mm²0.5095.09 V (1.27%)0.6096.09 V (1.52%)
6 mm²0.3393.39 V (0.85%)0.4064.06 V (1.01%)

If you use the one-way length in the DC formula, you get 1.24 V for the 100 ft, 10 AWG case instead of 2.48 V.

On the AC run, 8 AWG passes a 3% target at 2.33% but misses 1%. For the inverter’s voltage window, see string sizing. To see where the run sits on the drawing, see the three-line diagram.

Does peak voltage drop equal the energy you lose?

No. The drop is highest at full current, and few hours reach it. So annual energy loss is smaller than the headline figure. Mayfield reports that about 3% of daylight hours in Phoenix, 0.47% in Atlanta and 0.11% in Seattle reach 1,000 W/m².

In our example the drop falls from 0.62% at 10 A to 0.31% at 5 A and 0.124% at 2 A. Module current roughly follows irradiance. Mayfield’s modelling used 400 W modules, 1,000 V and 1,500 V string inverters and code-minimum 12 AWG wire. It found effective DC wire losses of 0.223% to 0.592% across its sites. That leaves out hours when the inverter limited power. It is a model, not a measurement.

Higher string voltage helps too. At the same 4,000 W and cable, a 600 V string carries 6.7 A instead of 10 A. Its drop percentage is 44% of the 400 V figure. See system losses for where wire loss sits in the loss chain.

Voltage drop calculator

Enter current, voltage, length, material, size and temperature. It gives the drop in volts and percent against your target.

Open the calculator on its own page

How solar software handles voltage drop

All five tools below report voltage drop on company pages read in October 2026, and only Easy PV states a limit (under 1%).

SoftwareCalculates or reports voltage drop?What it shows
Aurora Solar (Instant Plan Sets)YesDrop per wire run in the plan set
PVcase Roof MountYesDrop for the whole string, both cables
HelioScopeYesDrop at STC next to each conductor
Easy PVYesSmallest cable with drop under 1%
SolargrafYesListed among its SLD and three-line calculations
  • Aurora Solar (Instant Plan Sets): The circuit table lists voltage drop. A setting adds circuit length and voltage drop per wire run to the conductor table on sheet PV-3. Aurora help page, updated 27 January 2026. No percentage limit stated on that page.
  • PVcase Roof Mount: Release notes say the drop is determined for the whole string, including both the negative and positive cables. It also suggests cable cross-sections on the SLD. PVcase release notes 1.40.1, no release date shown.
  • HelioScope: Shows the STC voltage drop next to each conductor and recalculates wire distances when equipment moves. HelioScope help, updated 9 July 2025. Calculation method and limit not described.
  • Easy PV: Picks the smallest cable cross-section with a drop under 1% of the voltage across the cable, using IEC 60228 / BS 6360 resistances. Easy PV FAQ, no absolute date shown. Temperature and length basis not stated.
  • Solargraf: A company blog lists voltage drop among its SLD and three-line tool calculations, with copper and aluminium. Blog only, undated.

Design tools that show drop per wire run are ranked in our list of the best solar design software. For larger sites, see the best commercial solar design software.

Common mistakes with voltage drop calculation

FAQs

What is an acceptable voltage drop for solar DC cables?

No single limit is mandatory for PV. The sources cite 3% (NEC informational note for branch circuits), 2% (Penn State, Huawei’s maximum) and under 1% (Huawei’s preference, Easy PV’s tool default). Confirm the target with your AHJ and equipment maker.

Is 2% voltage drop required by the NEC?

No. Mayfield Renewables says the NEC contains no firm 2% requirement for PV. Penn State’s notes say the NEC does not require the calculation and recommends a maximum of 3%. Your adopted code edition and AHJ decide what applies.

Do I use one-way or round-trip length?

Use the loop length in the resistance. It is twice the one-way run for DC and two-wire AC. Balanced three-phase uses 1.732 times the one-way run instead. Penn State’s notes say this for DC and single-phase AC. PVcase Roof Mount states that it counts both the negative and positive cables.

Does aluminium need a bigger size than copper?

For the same drop, yes, by a little more than one size. In OpenExamPrep’s table, 8 AWG aluminium (1.26 ohm per 1,000 ft) is slightly worse than 10 AWG copper (1.21). That is a study-guide estimate, so use the maker’s aluminium table, and check ampacity separately.

  • Wire and conductor sizing: choosing conductor size from current, derating and voltage drop.
  • String sizing: choosing how many modules go in series and parallel.
  • NEC 690: the US code article for PV wiring and safety.
  • Watt, volt and amp: the three units that describe a circuit.

Next step: run your longest string through the calculator, then see which tools print drop per wire run in the best solar design software. For commercial string and feeder runs, see the best commercial solar design software.

Sources

Last updated 30 October 2026. Next scheduled review: 30 January 2027.

See the software on your shortlist.

Tell the SolarSoftwares team what you want in your solar software.

Your request goes by email to the SolarSoftwares team. A demo time is set only after we reply.